|
Keep Freeze Damage From Putting
a Chill in Irrigation Systems
by Lynda Wightman
- member of the NIAAA Sports Turf Advisory Committee
Every year, it's a ritual. From Maine
to Minnesota to Montana - and anywhere the frost level
could extend below the depth of installed pipe - getting
an irrigation system ready for the change of seasons
is annual event.
Coaches and sports turf managers need
to be aware that over the years, the effects of repeated
water expansion inside pipes can weaken those pipes
and lead to fractures. Plus, if the fittings and the
pipe do not expand and contract at the same rate during
seasonal temperature changes, the matter of material
stress will be called into question.
Of course, if your system contains PVC
pipe, there is no question. Because, when it's more
than half full of water and frozen, PVC pipe will crack
- most often from fitting to fitting (i.e., along the
length of the pipe).
You need to "winterize" your system to protect
it. The only question is: "how?"
"Blowing Out" a System
With an Air Compressor.
Unless your system has manual or automatic
drains, you will need to "blow out" water
in the system with a portable air compressor in order
to winterize. And doing it all is rather easy.
After turning off the water, connect
the compressor (100 CFM for pipe with 2" diameter
or less, 250 CFM for pipe 4" or larger) to inject
air into the system near the main shutoff. This could
be a quick coupler valve and/ or a special valve installed
for blowouts. Turn off the compressor and activate the
zone of sprinklers at the highest elevation and furthest
from the compressor before opening the valve on the
compressor. Be careful to introduce air into the system
gradually to avoid high-pressure surges. Then, slowly
increase the air pressure to 50 psi to reduce the chance
of water ram damaging the components. If the sprinkler
heads do not pop up and seal, adjust the pressure upward
until they do, but NEVER let the air pressure exceed
80 psi. It is not necessary and will have lasting harmful
affects on the system components.
It usually takes about two minutes or
more to evacuate each zone. Proceed in sequence through
all the zones, eventually ending up at the part of the
system closest to the compressor and at the lowest elevation.
Go twice through the entire system, using
a short cycle on each pass rather than a single long
one, as repeating the process completely removes water
that has drained from one zone into another on the first
cycle. It also helps reduce the amount of time compressed
air is moving through dry pipes (such friction can cause
heat damage).
Some Final Steps:
Got a controller? Be sure to leave your power on and
the rain or station start switch in the off position to
prevent condensation inside the controller enclosure.
Have a backflow device with ball valves? After shutting
off the water supply and draining the system, remove any
water trapped in the valve bodies by opening and closing
them several times with the lever handle. Then, leave
the handle at a 45-degree angle, so the valve is partially
open. Remove or wrap backflow device if necessary. Preparing
a hydraulic control system? Close and disconnect the potable
water supply line to the signal control tubing and drain
the tubing.
Use a submersible pump? Remove the pressure relief valve
and then “blow out” the lines with compressor
as mentioned above. Re-install the relief valve and drain
the pump (plug and/ or other valve). Make sure you remove
the suction lines and take time to inspect and repair
if required. In all cases, follow the manufacturer’s
procedures.
That's it. Whether your system is a football field Indianapolis,
a soccer field in Rochester or on a multi-function field
in Saskatoon, the same rules apply. To prevent freeze
damage you have to winterize your pipes.
"BLOW-OUT" WINTERIZATION CHECKLIST
• Don't allow air pressure to exceed 80 psi (especially
in systems designed to operate below this pressure level)
• Don't stand over component parts while the system
is under air pressure
• Don't leave the compressor unattended
• Don't blow out the system through a pump (first
blow out the system, then drain the pump)
• Don't leave manual drain valves open (water could
enter the system during a winter thaw)
|